Impedance & Inductance Tool

Transformer Inductance
Calculator

Calculate transformer leakage reactance and inductance from kVA, voltage, and % impedance. Also computes rated current and available short-circuit current.

Background

Leakage Reactance & Fault Current

01
Base Impedance

The base impedance relates per-unit values to ohms. For any transformer: Z_base = V² / (kVA × 1000). This normalises the transformer's rated voltage and capacity into a reference impedance from which all actual values are derived.

02
Leakage Reactance

%Z (percentage impedance) is the fraction of rated voltage needed to circulate rated current through the short-circuited transformer. Leakage reactance XL = (%Z/100) × Z_base in ohms. Most of the transformer impedance is inductive, so %Z ≈ %XL for design purposes.

03
Inductance in mH

Inductance L = XL / (2π × f). For a 500 kVA, 480 V transformer at 5% impedance, this is approximately 2.9 mH. This value is used in filter design, drive input reactor sizing, and harmonic current calculations.

04
Short-Circuit Current

The maximum available fault current at the transformer secondary is: Isc = I_rated / (%Z/100). For a 500 kVA / 480 V unit at 5% impedance, rated current ≈ 601 A and Isc ≈ 12,000 A. Protective devices must have an interrupting rating exceeding this value.

Formulas
Base Impedance (Ω)
Z_base = V² / (kVA × 1,000)
Leakage Reactance (Ω)
X_L = (%Z / 100) × Z_base
Inductance (mH)
L = X_L / (2π × f) × 1,000
Short-Circuit Current (A)
I_sc = I_rated / (%Z / 100)
Typical %Z by Size & Application
< 300 kVA2.0 – 4.0%Distribution, LV Dry-Type
300 – 1000 kVA4.0 – 5.5%Medium Distribution
1 – 10 MVA5.5 – 7.0%Substation / Power
> 10 MVA7.0 – 12%HV Power Transformers
FAQ

Leakage inductance (also called leakage reactance when expressed in ohms) represents magnetic flux that links only one winding and does not transfer energy to the other. It acts as a series impedance that limits fault current, causes voltage regulation under load, and determines the transformer's short-circuit impedance (%Z).

%Z determines the maximum available fault current at the transformer's secondary terminals. Lower %Z means higher fault current, requiring protective devices (breakers, fuses) with higher interrupting ratings. Higher %Z limits fault current but increases voltage regulation at load. Typical values: 2–4% for distribution, 5–7% for power transformers.

Leakage reactance XL = (Z%/100) × (V²/kVA×1000) in ohms. Inductance L = XL / (2π × f) in henries. These values are used in harmonic filter design, reactor sizing, cable impedance calculations, and short-circuit studies per IEC 60909 or ANSI C37.

Enter the secondary line-to-line voltage (e.g. 480 V, 600 V, 4160 V). The base impedance formula V²/(kVA×1000) uses line-to-line voltage for three-phase systems and gives per-phase results on a per-unit base. The short-circuit current uses line current (= kVA/(√3×V)).

Inductance Calculator

Need %Z or Loss Data for a Specific Unit?

Our engineering team can provide factory test reports, nameplate data, and impedance certificates for any Candron transformer, including custom-wound units.